48 or 24 VDC battery system. A fast-acting transfer switch ensures voice and data transmissions remain
uninterrupted in the event of a power grid failure or if the site utility power is disconnected for maintenance
and upgrade purposes. Built in a 2RU case adaptable for 19 and 23 rack installations.
Features
Pure sine wave AC output powers telecom equipment without performance degradation
Continuous duty rated full output wattage maintained even during extended power outages
1000 VA and 2000 VA models available easily cascaded for N+1 redundancy, providing maximum reliability
required by data centers
Low EMI and RFI interference characteristics
User-friendly Status and Diagnostic LCD/LED displays
Utility bypass function with fast load transfer switch
Remote Power Management optional via RS-232 port
Optional SNMP card
Numerous circuit and load protections over-current, over- temp, overload, reverse polarity, high/low battery
voltage
Form C alarm contacts for monitoring AC Fault and DC Abnormal conditions
Adapts for 19 or 23 racks; occupies only 2 RU (3.5)
UL and cUL listed
Specifications
Model
|
DC Input
|
AC Output
|
||
Voltage
|
Amps
|
KVA
|
Watts
|
|
48-1000RM
|
40-60
|
25
|
1 KVA
|
800
|
48-2000RM
|
40-60
|
50
|
2 KVA
|
1600
|
24-1000RM
|
20-30
|
50
|
1 KVA
|
800
|
125-1000RM
|
100-150
|
10
|
1 KVA
|
800
|
125-2000RM
|
100-150
|
20
|
2 KVA
|
1600
|
48-1000IRM*
|
40-60
|
25
|
1 KVA
|
800
|
48-2000IRM*
|
40-60
|
50
|
2 KVA
|
1600
|
* I series models use IEC type AC output
connector
AC Characteristics
Voltage:
100/110/115/120 VAC (selectable using RS-232 port and additional
software); Factory set at 115 VAC
Frequency:
60 Hz. Standard, 50 Hz. Optional
Regulation:
+/- 2%
Wave Form:
Pure Sine
Outlets Rear Panel:
24-1000RM and 48-1000RM (4 ea.) NEMA 5-15R
48-2000RM (4 ea.) NEMA 5-20R
Total Harmonic Distortion:
6% 120V/100% linear load 4% 120V/100% SPS load
Transfer Time:
<4 ms.
Displays
LED:
Inverter On, Overload, DC Abnormal, Fault
LCD:
Inverter On, Output Voltage and Frequency, Input Voltage, Load
Percentage, DC Voltage, System Model,
Internal Environment Temperature, Utility Status, Short Circuit, Over
Temperature
Operating Temperature:
0° to 45° C
Cooling:
Forced air, front-to-back
Humidity:
0-90% relative humidity
Acoustic Noise:
46 dBA @ 1 M
Alarms
Form C
(Dry Contact) terminals (two sets DC ABNORMAL and FAULT)
Communication Interface
RS-232 port, serial cable included
Protection Features
DC Input Fuse and Breaker, AC Input
Breaker, Output Breaker, Short Circuit, Overload, Over
Temperature, Over/Under Output Voltage, Over/Under Input Voltage, Fan
Failure Detection
Mechanical
Dimensions:
17.4W x 3.5H x 11.6D
Mounting:
19 or 23 Rack
Weight:
24-1000RM and 48-1000RM 15.4 Lbs., 48-2000RM 17.6 Lbs.
Options
Remote monitor via RS 232 port. SNMP
card required.