Newmar 48-24-15RM DC Converter 40-60 VDC To 24VDC, 15A
Communication sites require isolated DC Converters to provide excellent
voltage regulation, low noise, and high efficiency voltage conversion.
Reliability is vital under continuous duty operation and high ambient
temperatures. All these aspects were incorporated in the design of our rackmount
DC Converters.
These units accept a wide input range at 24 or 48 VDC nominal, positive or
negative ground, and produce pure 12 or 24 volt power. The solid state circuitry
is conservatively designed and semi-conductors are selected and tested to
withstand 200% of normal operating power.
Output voltage is maintained within 1% for all line and load conditions and
the output is well filtered, allowing use with sensitive transceivers and
telecom equipment.
Features
- 48, 24 volt inputs; 12, 24 volt outputs; positive, negative or floating
ground.
- Input/Output chassis isolation – 250 VDC
- 400 watt output
- Rated for continuous duty at full load.
- Excellent regulation under all line/load conditions.
- Low ripple provides noise free output.
- High efficiency – 87% typical.
- Easily adapts to both 19" and 23" racks, center mount (6" from front)
- Output volt and ammeter
- Output voltage adjustment on front panel
- Low profile – occupies two RU (one RU space above and below recommended
for cooling)
Specifications
Model |
Input |
Voltage
(VDC) |
Output
Adjustment |
Amperage
(continuous) |
Weight |
Voltage
(VDC) |
Max
Amps |
Lbs |
Kg. |
48-12-30RM |
40-60 |
12 |
13.6 |
12.6-14.5 |
30 |
10 |
4.6 |
48-24-15RM |
40-60 |
12 |
27.2 |
25.2-29.0 |
15 |
10 |
4.6 |
24-48-8RM |
20–30 |
26 |
54.4 |
50.4-58.0 |
8 |
10 |
4.6 |
Performance
- Regulation: 1% line/load
- Ripple: +/– 1/2% peak-peak max.
- Idle Current: 48V: <100 mA, 24V: 300 mA
- Efficiency: 85% typical @ 50% load.
- Operating Temperature: -20 to 50° C; Derate linearly from 100% @ 50° C to
50% @ 70° C
- Isolation: 250 volts input-out put-chassis.
Rear View
Mechanical
- Powder coated aluminum front panel, vinyl coated aluminum case.
- Mounting brackets provided for 19" or 23" rackmount, center or front.
- Easy access terminal blocks on back of unit, with protective cover
- Front panel switch guard provided.
- Output voltage adjustment potentiometer recessed in front panel
Protection
- Input and Output circuit breaker.
- Current limited/short circuit proof.
- High/low input voltage shutdown
- Fail-safe components guard against output over-voltage condition.
- Automatic high temperature power reduction starting at 65° C heat sink
temp.
- Automatic thermal shut down and recovery @ 80° C heat sink temp.
(automatic reset @ 55° C heat sink temp.).
- Reverse polarity protection.
Options
- Operation as battery charger and /or parallel redundant operation. (Heat
sink mounted oring diode installed in series with the output)
- Output Failure Alarm Contacts; Form C
- Current protection recommended on charging leads
Case Size R-1
Inches |
Centimeters |
H |
W |
D |
H |
W |
D |
3.5 |
19/23 |
14 |
8.9 |
48.3/58.4 |
35.6 |
|